Check to make sure the connection cable is correct before matching
Start matching
First, press and hold the previous page at the same time when booting
Second, wait for 15 seconds to start the interface, select in Select>- enter 3
three. Appear after 15s, set the manufacturer Ceneral Purpose to Fronius
Sometimes the manufacturer is Fronius, set to Ceneral Purpose, OK. Changed back to Fronius
four. The type is set to TS/TPSwith Dnet, it is determined that the cold boot and then the boot is started normally.
1. Cold boot press FCTN function key
Fives. After booting up, the following interface appears, Enter the Device MACID: 2 input 2,
Reset IO, select No
six. Set the DevioceNet board to ON state
Seven. Arc welding software setup, multiple welding condition processing: enabled
Eight. Set the digital output signal
(DO121) usually weld Seave (start welding)
(DO122) Reverse Robot Peady (preparation)
After the above settings are completed, confirm the wire feeding through the teach pendant, and the wire can be matched with OK.
Some problems after the match is completed:
1. The alarm information is: (ARC-025 is activated after welding)
Activate after welding
Setting method: variable—AWEPCR—AWEPCR—T—AE-CHK—DI—FALSE
2. The motherboard is not found
Check DevioceNet plug wiring
From top to bottom (1 red 2. white 3. silver 4. blue 5. black)
Five-hole anti-collision method: connect a 120Ω resistor between white and blue
The motherboard is as shown, the DevioceNet cable is connected to the above OK.