Model Number | SUP1 |
SPD according IEC 61643-1 | Class II |
SPD according EN 61643-11 | Type 2 |
Operating Temperature Range | -40ºC~+80ºC |
Relative Humidity | ≤95%(25ºC) |
Atmospheric Pressure | 86~106kPa |
Working Frequency | 50/60Hz |
Rated Working Voltage Uo | 230V/400V~ |
Max Continuous Operating Voltage Uc(L-N) | 275V/320V/385V/420V ~ |
Mode of protection | L-N/N-PE |
Nominal Discharge Current In(8/20μs)(L-N) | 20kA |
Max Discharge Current Imax (8/20μs) (L-N) | 40kA |
Voltage Protection Level Up(L-N) | ≤1.2kV |
Max. mains-side Overcurrent Protection | 80A(gL/gG) |
Cross sectional area for wiring terminal connected to conductor | Stranded:4~25mm² Solid Wire: 4~35mm² |
Max. Cross-sectional Area For Remote Signaling Interface | 1.5mm² |
Torque: wiring terminal/remote signaling interface | 2.5Nm |
Enclosure material | PBTV-0 |
Degree of protection(IP code) | IP20 |
Mounting | DIN35mm rails |
SUP2-PV series surge protector | SUP4-PV | ||
PV DC specific (LEC 6614-1/EN 61643-11) | |||
Pole | 2 pole | 3 pole | |
Electrical Parameter | |||
Classifical test | II | II | |
Uoc max (V DC) | 500 | 900 | |
Uc (V DC) | 500 | 1000 | |
In(8/20)us (KA) | 20 | 20 | |
Imax(8/20)us (KA) | 40 | 40 | |
Up (KV) | 2.0 | 3.8 | |
Remote control and indication | |||
Indication window | |||
Plug-in module | |||
Remote signal contact | |||
Remote signal contact | Max working volt | 250V AC/30V DC | 250V AC/30V DC |
Max working amp 1A (250V/AC) | 1A (250V/AC) | 1A (250V/AC) | |
1A (30V DC) | 1A (30V DC) | 1A (30V DC) | |
Wiring & installation | |||
Wiring capacity(mm2) | Hard wire | 4-25 | 4-25 |
 |
Flexible wire | 4-16 | 4-16 |
Stripping length | 10 | 10 | |
Terminal screwa | M5 | M5 | |
Torque(Nm) | Main ciruit | 3.5 | 3.5 |
Remote signal contact | 0.25 | 0.25 | |
Protection class | All profile | IP40 | IP40 |
Connection port | IP20 | IP20 | |
Installation environment | No obvious shock and vibration | ||
Altitude(m) | ≤ 2000 | ≤ 2000 | |
Working temperature | -3.0--+70 | -3.0--+70 | |
Relative humidity | 30%-90% | 30%-90% | |
How to install | Install with H35-7.5/DIN35 stell mounting rail | ||
Size(mm) (W*H*L) | W | 36 | 54 |
H | 90 | 90 | |
L | 67.6 | 67.6 | |
Weight (KG) | 0.25 | 0.38 |
Nominal PV system volt | 600V | 100V | 1200V |
MCOV(UCPV) | 700V DC | 1170V DC | 1200V DC |
Max system discharge Current (8/20us) (Imax) | 40KA | 40KA | 30KA |
Volt protection leve (UP) | ≤ 2.5KV | ≤ 4.0KV | ≤ 4.5KV |
Volt protection Level at 5KA (UP) | ≤ 2.0KV | ≤ 3.5KV | ≤ 4.0KV |
Integrate fuse breaking capacity/interrupting rating | 30KA/1000V DC | 30KA/1000V DC | 30KA/1200V DC |
Technology | Short-circuit interruption (SCI) overcurrent protection | ||
Operating temperature range | -40 to +80 | ||
Nominal discharge current | 12.5KA | ||
Response time (ta) | <25ns | ||
Operating state/fault indication | Green (good) / Red (replace) | ||
Mounting | 35mm DIN Rail per EN 60715 | ||
Degree protection | IP20 | ||
capacity | 3 modules DIN 43880 |