Relay This is an industrial electrical appliance that is now more common. For the choice of relays, many consumers are not very clear. For relay selection, what should we choose? Below we invite the editor of China Relay Network to take me to learn more about it.
Type selection:
Under normal circumstances, two-phase thermal relays can be used. However, when the three-phase voltage is poorly balanced and the working environment is poor or unattended, a three-phase thermal relay should be used. For delta-connected motors, thermal relays with phase failure protection should be used.
1, thermal relay rated current selection:
The rated current of the thermal relay should be greater than the rated motor current. Then select the thermal relay model based on the rated current.
2. Selection and setting of rated current of thermal element:
The rated current of the thermal element should be slightly larger than the rated current of the motor. When the starting current of the motor is 6 times of its rated current and the starting time does not exceed 5S, the setting current of the thermoless part is adjusted to be equal to the rated current of the motor; when the motor starts for a long time, the impact load is dragged or the parking is not allowed. When the thermal element setting current is adjusted to 1.1-1.15 times the rated current of the motor.
LYF Copper Lube Terminals
Our company specializes in the production and sales of all kinds of terminals, copper terminals, nose wire ears, cold pressed terminals, copper joints, but also according to customer requirements for customization and production, our raw materials are produced and sold by ourselves, we have their own raw materials processing plant, high purity T2 copper, quality and quantity, come to me to order it!
LYF Copper Lube Terminals,Ring insulated terminals
Taixing Longyi Terminals Co.,Ltd. , https://www.txlyterminals.com